Type designation: SL2-3x/3A/RTU/3W/1/250-1
Article number: L223107001Z00
Descriptionaccording to EN60947-3, size NH2 - 400A
- 1pole switchable, DELTA-contact system
- for mounting on 3pole busbar system with 185mm centre-to-centre distance
- with screw terminal M12
- 3 current-transformer 250-1 mounted and wired
- with integrated measuring system PLPLANO
- 3-phase for current, voltage, power, power factor, energy [kWh]
- integrated four-quadrant energy meter with detection of the energy flow direction
- secondary current detection via current transformers, if necessary for on-site exchange / retrofitting
- wired and routed to interface module
- wired with internally protected voltage tap, routed to the interface module
- Data interface protocol: ModBus / RTU
- with point-symmetrical and reverse-polarity protected plug connection
- Number of bus users: <= 16
- Installation dimension L2 until top edge of the strip (including data interface): <= 310mm
- Measuring system can be replaced without tools
Rated operating current Ie: | 250 A |
Cable terminal: | Flat terminal M12 |
Poles: | 3 |
Switching mode: | 1pole switchable |
Current measurement: | Integrated, 3phase |
number of current-transformer: | 3 |
Primary current of current-transformer: | 250 A |
Secondary rated current transformer Isr: | 1 A |
Datenerfassungsmodul PLPlano: | ModBus/RTU Elektrische Kenngrößen
Anzeige
|
Type designation: SL2-3x/3A/RTU/3W/1/250-1
Article number: L223107001Z00
Descriptionaccording to EN60947-3, size NH2 - 400A
- 1pole switchable, DELTA-contact system
- for mounting on 3pole busbar system with 185mm centre-to-centre distance
- with screw terminal M12
- 3 current-transformer 250-1 mounted and wired
- with integrated measuring system PLPLANO
- 3-phase for current, voltage, power, power factor, energy [kWh]
- integrated four-quadrant energy meter with detection of the energy flow direction
- secondary current detection via current transformers, if necessary for on-site exchange / retrofitting
- wired and routed to interface module
- wired with internally protected voltage tap, routed to the interface module
- Data interface protocol: ModBus / RTU
- with point-symmetrical and reverse-polarity protected plug connection
- Number of bus users: <= 16
- Installation dimension L2 until top edge of the strip (including data interface): <= 310mm
- Measuring system can be replaced without tools
Rated operating current Ie | 250 A |
Cable terminal | Flat terminal M12 |
Poles | 3 |
Switching mode | 1pole switchable |
Current measurement | Integrated, 3phase |
number of current-transformer | 3 |
Primary current of current-transformer | 250 A |
Secondary rated current transformer Isr | 1 A |
Datenerfassungsmodul PLPlano | ModBus/RTU Elektrische Kenngrößen
Anzeige
|
Type designation: SL2-3x/3A/RTU/3W/1/400-1
Article number: L223107004Z00
Descriptionaccording to EN60947-3, size NH2 - 400A
- 1pole switchable, DELTA-contact system
- for mounting on 3pole busbar system with 185mm centre-to-centre distance
- with screw terminal M12
- 3 current-transformer 400-1 mounted and wired
- with integrated measuring system PLPLANO
- 3-phase for current, voltage, power, power factor, energy [kWh]
- integrated four-quadrant energy meter with detection of the energy flow direction
- secondary current detection via current transformers, if necessary for on-site exchange / retrofitting
- wired and routed to interface module
- wired with internally protected voltage tap, routed to the interface module
- Data interface protocol: ModBus / RTU
- with point-symmetrical and reverse-polarity protected plug connection
- Number of bus users: <= 16
- Installation dimension L2 until top edge of the strip (including data interface): <= 310mm
- Measuring system can be replaced without tools
Rated operating current Ie: | 400 A |
Cable terminal: | Flat terminal M12 |
Poles: | 3 |
Switching mode: | 1pole switchable |
Current measurement: | Integrated, 3phase |
number of current-transformer: | 3 |
Primary current of current-transformer: | 400 A |
Secondary rated current transformer Isr: | 1 A |
Precision of category of the current transformers: | Class 1 |
Datenerfassungsmodul PLPlano: | ModBus/RTU Elektrische Kenngrößen
Anzeige
|
Type designation: SL2-3x/3A/RTU/3W/1/400-1
Article number: L223107004Z00
Descriptionaccording to EN60947-3, size NH2 - 400A
- 1pole switchable, DELTA-contact system
- for mounting on 3pole busbar system with 185mm centre-to-centre distance
- with screw terminal M12
- 3 current-transformer 400-1 mounted and wired
- with integrated measuring system PLPLANO
- 3-phase for current, voltage, power, power factor, energy [kWh]
- integrated four-quadrant energy meter with detection of the energy flow direction
- secondary current detection via current transformers, if necessary for on-site exchange / retrofitting
- wired and routed to interface module
- wired with internally protected voltage tap, routed to the interface module
- Data interface protocol: ModBus / RTU
- with point-symmetrical and reverse-polarity protected plug connection
- Number of bus users: <= 16
- Installation dimension L2 until top edge of the strip (including data interface): <= 310mm
- Measuring system can be replaced without tools
Rated operating current Ie | 400 A |
Cable terminal | Flat terminal M12 |
Poles | 3 |
Switching mode | 1pole switchable |
Current measurement | Integrated, 3phase |
number of current-transformer | 3 |
Primary current of current-transformer | 400 A |
Secondary rated current transformer Isr | 1 A |
Precision of category of the current transformers | Class 1 |
Datenerfassungsmodul PLPlano | ModBus/RTU Elektrische Kenngrößen
Anzeige
|
Type designation: SL2-3x/9/KM2G-F/RTU/3W/1/400-1
Article number: L229607005Z00
Descriptionaccording to EN60947-3, size NH2 - 400A
- 1pole switchable, DELTA-contact system
- for mounting on 3pole busbar system with 185mm centre-to-centre distance
- with v-terminal and steel-frame clamp type KM2G-F, max. clamping range: 25-240mm²
- 3 current-transformer 400-1 mounted and wired
- with integrated measuring system PLPLANO
- 3-phase for current, voltage, power, power factor, energy [kWh]
- integrated four-quadrant energy meter with detection of the energy flow direction
- secondary current detection via current transformers, if necessary for on-site exchange / retrofitting
- wired and routed to interface module
- wired with internally protected voltage tap, routed to the interface module
- Data interface protocol: ModBus / RTU
- with point-symmetrical and reverse-polarity protected plug connection
- Number of bus users: <= 16
- Installation dimension L2 until top edge of the strip (including data interface): <= 310mm
- Measuring system can be replaced without tools
Rated operating current Ie: | 400 A |
Cable terminal: | V box terminal KM2G-F 25-240mm² |
Poles: | 3 |
Switching mode: | 1pole switchable |
Current measurement: | Integrated, 3phase |
number of current-transformer: | 3 |
Primary current of current-transformer: | 400 A |
Secondary rated current transformer Isr: | 1 A |
Precision of category of the current transformers: | Class 1 |
Datenerfassungsmodul PLPlano: | ModBus/RTU Elektrische Kenngrößen
Anzeige
|
Type designation: SL2-3x/9/KM2G-F/RTU/3W/1/400-1
Article number: L229607005Z00
Descriptionaccording to EN60947-3, size NH2 - 400A
- 1pole switchable, DELTA-contact system
- for mounting on 3pole busbar system with 185mm centre-to-centre distance
- with v-terminal and steel-frame clamp type KM2G-F, max. clamping range: 25-240mm²
- 3 current-transformer 400-1 mounted and wired
- with integrated measuring system PLPLANO
- 3-phase for current, voltage, power, power factor, energy [kWh]
- integrated four-quadrant energy meter with detection of the energy flow direction
- secondary current detection via current transformers, if necessary for on-site exchange / retrofitting
- wired and routed to interface module
- wired with internally protected voltage tap, routed to the interface module
- Data interface protocol: ModBus / RTU
- with point-symmetrical and reverse-polarity protected plug connection
- Number of bus users: <= 16
- Installation dimension L2 until top edge of the strip (including data interface): <= 310mm
- Measuring system can be replaced without tools
Rated operating current Ie | 400 A |
Cable terminal | V box terminal KM2G-F 25-240mm² |
Poles | 3 |
Switching mode | 1pole switchable |
Current measurement | Integrated, 3phase |
number of current-transformer | 3 |
Primary current of current-transformer | 400 A |
Secondary rated current transformer Isr | 1 A |
Precision of category of the current transformers | Class 1 |
Datenerfassungsmodul PLPlano | ModBus/RTU Elektrische Kenngrößen
Anzeige
|
Type designation: SL2-3x/9/RM300/RTU/3W/1/250-1
Article number: L229907003Z00
Descriptionaccording to EN60947-3, size NH2 - 400A
- 1pole switchable, DELTA-contact system
- for mounting on 3pole busbar system with 185mm centre-to-centre distance
- with v-terminal and aluminium box clamp clamp type RM300, max. clamping range: 25-300mm²
- 3 current-transformer 250-1 mounted and wired
- with integrated measuring system PLPLANO
- 3-phase for current, voltage, power, power factor, energy [kWh]
- integrated four-quadrant energy meter with detection of the energy flow direction
- secondary current detection via current transformers, if necessary for on-site exchange / retrofitting
- wired and routed to interface module
- wired with internally protected voltage tap, routed to the interface module
- Data interface protocol: ModBus / RTU
- with point-symmetrical and reverse-polarity protected plug connection
- Number of bus users: <= 16
- Installation dimension L2 until top edge of the strip (including data interface): <= 310mm
- Measuring system can be replaced without tools
Rated operating current Ie: | 250 A |
Cable terminal: | V-type aluminium box terminal RM300 |
Poles: | 3 |
Switching mode: | 1pole switchable |
Current measurement: | Integrated, 3phase |
number of current-transformer: | 3 |
Primary current of current-transformer: | 250 A |
Secondary rated current transformer Isr: | 1 A |
Datenerfassungsmodul PLPlano: | ModBus/RTU Elektrische Kenngrößen
Anzeige
|
Type designation: SL2-3x/9/RM300/RTU/3W/1/250-1
Article number: L229907003Z00
Descriptionaccording to EN60947-3, size NH2 - 400A
- 1pole switchable, DELTA-contact system
- for mounting on 3pole busbar system with 185mm centre-to-centre distance
- with v-terminal and aluminium box clamp clamp type RM300, max. clamping range: 25-300mm²
- 3 current-transformer 250-1 mounted and wired
- with integrated measuring system PLPLANO
- 3-phase for current, voltage, power, power factor, energy [kWh]
- integrated four-quadrant energy meter with detection of the energy flow direction
- secondary current detection via current transformers, if necessary for on-site exchange / retrofitting
- wired and routed to interface module
- wired with internally protected voltage tap, routed to the interface module
- Data interface protocol: ModBus / RTU
- with point-symmetrical and reverse-polarity protected plug connection
- Number of bus users: <= 16
- Installation dimension L2 until top edge of the strip (including data interface): <= 310mm
- Measuring system can be replaced without tools
Rated operating current Ie | 250 A |
Cable terminal | V-type aluminium box terminal RM300 |
Poles | 3 |
Switching mode | 1pole switchable |
Current measurement | Integrated, 3phase |
number of current-transformer | 3 |
Primary current of current-transformer | 250 A |
Secondary rated current transformer Isr | 1 A |
Datenerfassungsmodul PLPlano | ModBus/RTU Elektrische Kenngrößen
Anzeige
|
Type designation: SL2-3x/9/RM300/RTU/3W/1/400-1
Article number: L229907006Z00
Descriptionaccording to EN60947-3, size NH2 - 400A
- 1pole switchable, DELTA-contact system
- for mounting on 3pole busbar system with 185mm centre-to-centre distance
- with v-terminal and aluminium box clamp clamp type RM300, max. clamping range: 25-300mm²
- 3 current-transformer 400-1 mounted and wired
- with integrated measuring system PLPLANO
- 3-phase for current, voltage, power, power factor, energy [kWh]
- integrated four-quadrant energy meter with detection of the energy flow direction
- secondary current detection via current transformers, if necessary for on-site exchange / retrofitting
- wired and routed to interface module
- wired with internally protected voltage tap, routed to the interface module
- Data interface protocol: ModBus / RTU
- with point-symmetrical and reverse-polarity protected plug connection
- Number of bus users: <= 16
- Installation dimension L2 until top edge of the strip (including data interface): <= 310mm
- Measuring system can be replaced without tools
Rated operating current Ie: | 400 A |
Cable terminal: | V-type aluminium box terminal RM300 |
Poles: | 3 |
Switching mode: | 1pole switchable |
Current measurement: | Integrated, 3phase |
number of current-transformer: | 3 |
Primary current of current-transformer: | 400 A |
Secondary rated current transformer Isr: | 1 A |
Datenerfassungsmodul PLPlano: | ModBus/RTU Elektrische Kenngrößen
Anzeige
|
Type designation: SL2-3x/9/RM300/RTU/3W/1/400-1
Article number: L229907006Z00
Descriptionaccording to EN60947-3, size NH2 - 400A
- 1pole switchable, DELTA-contact system
- for mounting on 3pole busbar system with 185mm centre-to-centre distance
- with v-terminal and aluminium box clamp clamp type RM300, max. clamping range: 25-300mm²
- 3 current-transformer 400-1 mounted and wired
- with integrated measuring system PLPLANO
- 3-phase for current, voltage, power, power factor, energy [kWh]
- integrated four-quadrant energy meter with detection of the energy flow direction
- secondary current detection via current transformers, if necessary for on-site exchange / retrofitting
- wired and routed to interface module
- wired with internally protected voltage tap, routed to the interface module
- Data interface protocol: ModBus / RTU
- with point-symmetrical and reverse-polarity protected plug connection
- Number of bus users: <= 16
- Installation dimension L2 until top edge of the strip (including data interface): <= 310mm
- Measuring system can be replaced without tools
Rated operating current Ie | 400 A |
Cable terminal | V-type aluminium box terminal RM300 |
Poles | 3 |
Switching mode | 1pole switchable |
Current measurement | Integrated, 3phase |
number of current-transformer | 3 |
Primary current of current-transformer | 400 A |
Secondary rated current transformer Isr | 1 A |
Datenerfassungsmodul PLPlano | ModBus/RTU Elektrische Kenngrößen
Anzeige
|